LVQB SF6 Insulated Current Transformer

Summary

The enclosure, locating at the top, could be divided into “T” shape and “bell-cover” shape. T shaped enclosure is made of anticorrosive aluminum; Bell-cover enclosure is made of casting aluminum. The enclosure is checked by intensity and gas sealing and X ray.

The main body (primary winding and secondary winding) is fixed in the enclosure. SF6 is adopted as the insulating medium between the primary winding and secondary winding in which has the shield tube supported by epoxy resin for the secondary winding. The outgoing line for the secondary winding is lead to the connection box in pedestal through down-lead tube.

  • Product Details
  • Sepcification
  • Make an Inquiry

Summary

The enclosure, locating at the top, could be divided into “T” shape and “bell-cover” shape. T shaped enclosure is made of anticorrosive aluminum; Bell-cover enclosure is made of casting aluminum. The enclosure is checked by intensity and gas sealing and X ray.

The main body (primary winding and secondary winding) is fixed in the enclosure. SF6 is adopted as the insulating medium between the primary winding and secondary winding in which has the shield tube supported by epoxy resin for the secondary winding. The outgoing line for the secondary winding is lead to the connection box in pedestal through down-lead tube.


Feature

1.The insulating tube, dividing into porcelain tube that is sintered by high-strength porcelain and silicon-rubber tube, and silicon-rubber porcelain which has better performances in resisting pollution,water invasion and electric corrosion comparing with that high-strength porcelain.

2.The pedestal is designed with connection box,SF6 gas density controller and gas filling valve. The Sf6 gas density controller provideds the functions as temperature compensation,alarm and remote monitor to the gas pressure.


Working condition:

Ambient temperature

maximum: +40°C

average temperature in a day: +30°C

minimum: -30°C(-40°C is available for particular order)

Height above sea level

within 1000 meters, while 3000 meters is the maximum for the altiplano-style

Air condition

There should be no heavily corrosive gas, no inflammable and explosive material;

Seismic intensity: 8 degree

Velocity: within 35m/s

Installation place: outdoor or indoor.


Main Technical Parameters

Type designate LVQB-35 LVQB-66/110 LVQB-220 LVQBT-500
Structure T shape Bell-cover shape T shape Bell-cover shape T shape Bell-cover shape Bell-cover shape
Rated voltage kV 35 66/110 220 500
Maximum voltage kV 40.5 72.5/126 252 550
Rated frequency Hz 50 50 50 50
Short-time power frequency withstand kV 95 160/230 460 740
Lightening full wave impulse voltage kV 200 350/550 950/1050 1550/1675
Partial discharge pC <5 <5 <5 <5
Rated primary current 50-2000 50-3000 100-3000 600-5000
Rated secondary current 5 or 1 5 or 1 5 or1 1
Accuracy class 0.2s;0.2 0.2s;0.2 0.2s;0.2 0.2s;0.2
0.5s;0.5 0.5s;0.5 0.5s;0.5 0.5s;0.5
5P;10P 5P;10P 5P;10P;TPY 5P;10P;TPY
Rated output VA 10-60 10-60 10-60 10-60
Meter protection factor FS 5;10 5;10 5;10 5;10
Accuracy limit factor 10;15;20;25;30
Short-time hot stability current kA/s 12.5-31.5/1 31.5-50/3 31.5-50/3 50-63/3
Rated dynamic stability current kA 31.5-125 80-125 80-125 125-160
SF6 rated pressure (20掳C) Mpa 0.4 0.4 0.4 0.5
SF6 filling pressure (20掳C) Mpa 0.35 0.35 0.35 0.45
SF6 annual leakage % <0.5 <0.5 <0.5 <0.5
SF6 moist content ppm <150 <150 <150 <150
Outline dimension A1 mm 1125/1250 2195 3600/3770 6695
A2 mm 610/570 1064 Max 1300/1440 2073
A3 mm 960/1000 1900 3180/3240 5913
Pedestal mounting hole dimension 4-φd1 4-φ22
4-φ22 4-φ22 4-φ26
B1XB2 mm 430X330 550X450 780X640 940X940
Primary connection board dimension C1 mm /30 50 50
C2 mm /10 15 20
C3 mm /50 80 80
4-φd2 4-φ9 4-φ18 4-φ18
Weight kg 100 400-500 900-1200 2300